Remote Split Freezer BHTZ170 Monoblock Unit at -18 °C @ + 32 °C Ambient 7.41 m³
Click Image for Gallery
Description:
Unit Model: BHTZ170
- Electronic control panel.
- Expansion device with thermal expansion valve.
- Solid core filter on liquid line.
- Pre-arrangement for room lighting connection and for door switch connection.
- Cable for door heater connection on all low temperature units.
- All the models are equipped with a fixed calibration low pressure switch; all three-phase units and the model BHTX122 are also equipped with a fixed calibration high pressure switch, in accordance with the “Pressure Equipment Directive” 97/23/EC. Anyway, on request the high pressure switch could be supplied also on units with voltage 230/1/50Hz.
- All the units are supplied with a remote control panel already connected to the unit through a 5 m long cable (on request we could supply different lengths up to 20 m).
- Direct drainage of condensate.
- Drain heater.
- Condensing unit installation on the external floor of the cold room as well as evaporator installation on the ceiling inside the cold room.
- Sight glass.
- All units are supplied with a liquid receiver, in accordance with the “Pressure Equipment Directive” 97/23/EC.
- Connection pipes couplings between condensing unit and evaporator have been realized without shut-off valves or weld neck flanges.
- Units suitable for external installation. Units recommended for use at ambient temperatures higher than 10°C. If units are mounted in Ambient temperature lower than 10°C, some accessories are needed.
Technical Data :
Condenser:
- Form: 1C2
- Fin pitch: 2,1
- Fans: 1x254
- Fan absorption: 1x68
- Airflow: 1000
Evaporator:
- Form: EVS1X254
- Fin pitch: 4,2/8,4
- Fans: 1x254
- Fan absorption: 1x73
- Airflow: 810
- Air-throw: 6
Refrigerating (W) - Room volume (m³)
Cold room temperature: - 18 °C
Ambient temperature: + 25°C
- W: 1164
- m³: 11,28
Ambient temperature: + 32°C
- W: 1028
- m³: 7,41
Ambient temperature: + 43°C
- W: 791
- m³: 2,66
Cold room temperature: -22 °C
Ambient temperature: + 25°C
- W: 1013
- m³: 8,1
Ambient temperature: + 32°C
- W: 882
- m³: 5,21
Ambient temperature: + 43°C
- W: 686
- m³: 1,92
Cold room temperature: - 25 °C
Ambient temperature: + 25°C
- W: 913
- m³: 6,27
Ambient temperature: + 32°C
- W: 783
- m³: 3,97
Ambient temperature: + 43°C
- W: 590
- m³: 1,4