Floor Mount Bi-Block OVFR1250 Monoblock Unit

Floor Mount Bi-Block OVFR1250 Monoblock Unit

Description:

Unit Model: OVFR1250

  • Electronic control panel.
  • Expansion device with thermal expansion valve.
  • Solid core filter on liquid line.
  • Pre-arrangement for room lighting connection and for door switch connection.
  • Cable for door heater connection on all low temperature units.
  • All units are equipped with a fixed calibration low pressure switch and high pressure switch, in accordance with the “Pressure Equipment Directive” 97/23/EC.
  • All the units are supplied with a remote control panel already connected to the unit through a 5 m long cable (on request we could supply different lengths up to 20 m).
  • Direct drainage of condensate.
  • Drain heater.
  • Condensing unit installation on the external floor of the cold room as well as evaporator installation on the ceiling inside the cold room.
  • Sight glass.
  • Solenoid valve on the liquid line in the forms 3I3-3I5 and in all models OVFR. On request it is available also in the models of the Forms 1I2-1I3-2I2-2I3.
  • All units are supplied with a liquid receiver with safety valve, in accordance with the “Pressure Equipment Directive” 97/23/EC.
  • Oil separator on discharge line in the models OVFR.
  • Pressure regulating valve on suction line in the models OVFR.
  • Liquid separator on suction line.
  • Connection pipes couplings between condensing unit and evaporator have been realized without unions or weld neck flanges.
  • Crankcase heater of compressor.
  • Condenser fan pressure switch.
  • Units suitable for external installation. Units recommended for use at ambient temperatures higher than 10°C. If units are mounted in Ambient temperature lower than 10°C, some accessories are needed.
  • Cover to protect the unit against the bad weather.


Technical Data :

Condenser:

  • Form: 3I5
  • Fin pitch: 2,1
  • Fans: 1x630
  • Fan absorption: 1x610
  • Airflow: 8230

Evaporator:

  • Form: EVB2X450B
  • Fin pitch: 7
  • Fans: 2x450
  • Fan absorption: 2x305
  • Airflow: 8600
  • Air-throw: 19


Refrigerating capacity (W) - Room volume (m³)

Cold room temperature: - 30 °C

Ambient temperature: + 25°C

  • W: 10939

Ambient temperature: + 32°C

  • W: 10513

Ambient temperature: + 43°C

  • W: 9884

Cold room temperature: -35°C

Ambient temperature: + 25°C

  • W: 9322

Ambient temperature: + 32°C

  • W: 8850

Ambient temperature: + 43°C

  • W:  8451

Cold room temperature: - 40°C

Ambient temperature: + 25°C

  • W:  7844

Ambient temperature: + 32°C

  • W:  7402

Ambient temperature: + 43°C

  • W: 7120 